CONVERTEUR DC/AC SINUS

New economic range of converters - invertors :

from 12 V to 110 V in DC...
…and from 200 VA to 9000

Optional presentation in rack 19'' or box

Example for the range 48 V

Type

Nominal
Power
Nominal
Peak
Dimensions
Case
(w x d x h)
Dimensions
rack 19''
(h x d)
 RMS DC/AC 548 500 VA 1200 VA 152 x 381 x 315 3U x 450
 RMS DC/AC 748 700 VA 1400 VA 152 x 381 x 315 3U x 450
 RMS DC/AC 1048 1000 VA 1700 VA 152 x 381 x 315 3U x 450
 RMS DC/AC 1548 1500 VA 2100 VA 245 x 560 x 480 4U x 450
 RMS DC/AC 2048 2000 VA 3500 VA 245 x 560 x 480 4U x 450
 RMS DC/AC 3048 3000 VA 5600 VA 245 x 560 x 480 5U x 450
 RMS DC/AC 5048 5000 VA 8500 VA 357 x 780 x 430 5U x 650
 RMS DC/AC 7048 7000 VA 12000 VA 357 x 780 x 430 5U x 650
 RMS DC/AC 9048 9000 VA 14000 VA 357 x 780 x 430 5U x 650
General specifications for the range 48 V
 Input Minimum : 39 V
  Maximum : 60 V
 Output tolerance 230 V +/- 5% from 0 to In
 Harmonic distortion < 7.5% to In
 Efficiency 90%
 Frequency 50 Hz +/- 0.01 %
 Form Sinusoidal signal
 Transfer time from the by-pass Nil
 Protection in input voltage By stopping on low or high voltage
  Fuse or circuit breaker input 12/24/48/72 or 100 V
 Protection in output Against overloads and short circuits
  Against leakages in output by circuit breaker
  Differential 30 ma
 Dielectric strength 2500 V
 Degree of protection according to IP 20 standards
 Insulation 10 MΩ
 Acoustic noise at 1 m 20 dB
 Air ventilation Forced air ventilation
 Temperature Operating temperature 0°C to + 45°C
  Storage temperature - 20°C to + 50°C
 Humidity up to 90% without condensation
 Termination  Input by ANDERSON connector
 Jack output  200 V 2P+T CEE
 MTBF 800 000 hours
 Option by pass static
Specifications for other voltages
 With large input ranges  MINI MAXI
 12 V 10.5 V 18 V
 24 V 19 V 43 V
 72 V 58 V 90 V
 110 V 90 V 130 V
Visual alarms
   Presence into the mains (case with by-pass)
 Low voltage presence
 Low battery voltage
 High internal temperature (62 °C)
 Stoppage on internal temperature that is too high (67 °C)
 Overload
 Operation on by-pass
European standards:
CEI 110-5 ; EN 55022 ; EN 60601-1-2 ; EN 50091 ; EN 50082-1 ; CEI 110