Technical Specifications :
> Input voltage :
- 230V -15%/+10% 50Hz+/-5%
- Protected by fuse
> Output voltage :
- 12V ( internal adjustment from 11.5V to 14V )
- +/-2% from 0 to In.
- Residual ripple : 60mV peak to peak
> Output current :
- 10A nominal voltage
- Protection contre les surcharges et les courts-circuits.
- Courant de court-circuit : 5A
> Protection against battery overvoltages :
- Switch-on threshold : >15V → outage of 230V on charger
- Switch-back threshold : <13V → validation of 230V on charger
> Alarms :
- Low battery : by contact closure with adjustable threshold from 10V to 12V
- Mains : by contact closure
> Max. consumed power 50A
> Wall box :
- Sizes : 300 x 150 x 120mm
- Weight : 6 kg
> Presentation on a rack :
- Sizes : 19' x 3U
- Weight : 8 kg
|
|
Photos for information purpose only
> Manual mode :
- Change into manual mode by a switch on front side (anticlockwise)
- Setting of Manual mode voltage by potentiometer on front side (anticlockwise )
- Setting range of the output voltage from 11.5V to 15V
- Overvoltage protection disabled
- Setting of the low battery thresholds and shut-off option
- Option : Shut-off of consumed power output on threshold adjustable from 9V to 11V
|